When a GoodWe Lynx Home battery seems to misbehave, look first at the hybrid inverter's settings, the link between battery and inverter, and the Wi-Fi dongle that feeds SEMS Portal. GoodWe's own answers for a battery that won't charge or discharge point mostly to settings, the battery communication link and the meter clamp. Three checks come first: read the alarm in the SEMS Portal app, look at the button light on the battery's power control unit, and look at the COM and WiFi lights on the inverter. If your inverter is an EHB model, read the recall notice below first.
Safety first
High voltage is present whenever a Lynx battery is running. GoodWe says not to dismantle, modify or move it while it works, and to call after-sales rather than touch any exposed copper. Its manual is written for trained technicians, so your role is to look, note and report.
Stop and get help straight away if you notice smoke, a burning or chemical smell, hissing, swelling, leaking liquid or unusual heat. Then:
- Leave the area and call 000. South Australia's Metropolitan Fire Service (MFS) asks callers to say a home battery is involved and to keep everyone out of any smoke or vapour.
- Don't try to put it out. GoodWe states that water and ABC dry powder extinguishers cannot put out a Lynx battery fire, and that a burning battery can give off poisonous gas.
- Avoid leaked electrolyte. GoodWe describes it as corrosive. Anyone who breathes it in or gets it on their skin or eyes should get medical help.
- Use the shutdown sign only if safe. It should be near your inverter or switchboard. Assume parts stay live afterwards.
If a Lynx Home F battery reports an Insulation Fault, GoodWe's instruction is not to touch it and to contact after-sales. A battery that has been hit, flooded or through a fire should stay off even if it seems fine, the MFS says, until someone qualified has inspected it.
Recall: GoodWe EHB series hybrid inverters
A recall was published on Product Safety Australia on 19 September 2025 (PRA 2025/20623). It covers GoodWe EHB models GW5K-EHB-AU-G11, GW8.6K-EHB-AU-G11 and GW9.99K-EHB-AU-G11, and GE-branded GEH5.0-1U-10, GEH8.6-1U-10 and GEH10-1U-10. The Lynx Home F G2 datasheet lists EHB inverters among its pairings.
The problem: if the bypass switch is set to bypass while the inverter runs in backup mode, it can push power into the grid. That risks serious electric shock for your household, electricians and line workers.
What to do:
- Check the model number on your inverter's label, or ask your installer.
- If it matches, don't move the bypass switch to bypass, and don't let anyone work on the system until the firmware is updated.
- The fix is firmware version 050531. GoodWe updates online inverters remotely, and offline ones need a technician visit.
- Contact GoodWe's recall team on 0488 851 481 or [email protected], quoting the PRA number.
Before you start: quick checks
- Open the Alarm tab in SEMS Portal. It lists current and recovered alarms. Tap one for details and take a screenshot.
- Read the battery's button light. Green blinking means standby or idle. Steady green means charging or discharging. Red blinking is an alarm while the battery checks itself, and steady red is a fault.
- Read the inverter's COM light (EH and EHB). Solid means the battery and meter are both talking to the inverter. A single blink means the battery link has failed, a double blink means the meter link has failed, and off means both have failed.
- Check for a blackout. A Utility Loss alarm means the inverter can't detect the grid. GoodWe's ET G2 manual says it clears once grid power returns.
- Allow for the weather. The Lynx Home F G2 datasheet gives a charging range of 0 to 50°C and a discharging range of minus 20 to 50°C. It also says charge and discharge power are derated with temperature and charge level.
- Note any changes. A new modem, Wi-Fi password, tariff or charge schedule can explain a sudden change in behaviour.
Common problems and what to do
| Symptom | Likely cause | What you can check | When to call the installer |
|---|---|---|---|
| Battery won't charge | Discharge time setting, full battery, cold, lost battery link | Battery level, button light, COM light | COM light shows a battery link failure |
| Battery won't discharge at night | Depth of discharge reached, household load too low, charge window active | Battery level, time of day and household load | Battery level is well above the floor and still idle |
| Offline in SEMS Portal | Router, password or internet change | Inverter WiFi light, router internet, router channel | Light stays off, or the dongle can't hold a connection |
| Nothing works in a blackout | Back-Up Supply or off-grid output not enabled, circuit not on backup, overload | BACK-UP light, which circuits are backed up | Backup has never worked |
| Red light on the battery | Alarm or fault | SOC lights pattern, alarm name | Steady red, or the alarm keeps returning |
| Beeping, heat or smell | Earth fault alarm or a possible battery fault | Nothing hands-on | Straight away, and call 000 for smoke or fire |
Battery won't charge
GoodWe's EHB manual gives two simple reasons the battery won't charge when solar exceeds the load: an active discharge time setting, or a battery that is already full. The manual also lists a failed BMS link and a misplaced or reversed current clamp (CT) as causes, which your installer checks in the SolarGo app.
A Lynx battery that stops short of 100 per cent is often working as set. GoodWe says charging stops once the battery reaches the charge cut-off level or charge voltage set in SolarGo. Our guide to a solar battery not charging covers causes common to every brand.
Battery won't discharge at night
The EHB manual's FAQ explains several reasons a charged battery sits idle. The house must draw more than 100 W before the battery will discharge continuously. The battery stops at the depth of discharge (DOD) floor, and a charge time window also blocks discharging while it is active.
Once the battery falls below its DOD floor, it won't discharge again until it recharges to halfway between 20 per cent and that floor. For example, with DOD set to 90 per cent, discharge stops at 10 per cent and resumes at 15 per cent.
Working mode matters too: GoodWe's ET G2 manual says Back-up mode holds charge for outages and Economic mode works to set times. See our guide to a battery that won't power the home at night for the bigger picture.
Offline in SEMS Portal
SEMS Portal only updates while the Wi-Fi dongle reaches the internet. On EH and EHB inverters, two blinks of the WiFi light mean it can't reach your router, and four blinks point to an internet or server problem.
GoodWe's help centre and ET G2 manual suggest these steps:
- Check that your router has working internet by loading a web page on another device, and restart it if needed.
- Move the router closer or add a Wi-Fi extender if the signal is weak.
- Check the router's wireless channel is 13 or lower. GoodWe advises changing it if it is higher.
- Check the router isn't filtering devices by MAC address.
- Redo the Wi-Fi setup in the SEMS Portal app, using the Configuration option on its login page.
GoodWe's Lynx Home F G2 warranty requires an internet connection for monitoring and warns the warranty may be void without one. Our battery offline guide has more general fixes.
Nothing works in a blackout
GoodWe's help centre explains that backup only covers loads wired separately to the inverter's BACK-UP port, usually lights, the fridge and the modem. Ovens and heaters often exceed the limit.
On EH and EHB inverters, the BACK-UP light is on when backup is ready and off when backup is off. The EHB manual says the Back-Up Supply setting must be turned on, plus the Off-Grid Output Switch for running without the grid. It also warns that restarting the inverter or battery after enabling the Off-Grid Output Switch turns it off again.
A Back-Up Over Load alarm means backed-up appliances drew more than the inverter can deliver. Ask your installer to confirm settings and wiring, since Australian sites also need specific neutral wiring for backup. Our blackout backup guide has more general checks.
Red light on the battery
When the button light turns red, check the five SOC lights, which can show a fault pattern instead of the charge level. The Lynx manual maps each pattern to a fault, such as overvoltage, cell temperature, insulation or relay problems. Take a photo of the lights before anything changes. Lynx Home F and F Plus+ batteries use a different fault table from the G2, also in GoodWe's ET G2 combined manual.
One common pattern is a flashing red button light, SOC lights showing the charge level, and no relay click at start-up. GoodWe links that to a communication fault or the wrong battery model chosen in SolarGo, both installer fixes. If the lights go out and the battery switch trips during operation, GoodWe points to a short circuit or an internal battery failure. Don't keep resetting it.
Beeping, heat or smell
GoodWe's EHB and ET G2 manuals say inverters for Australia and New Zealand sound a buzzer when they detect an insulation fault. It sounds for one minute and then every 30 minutes until fixed. Treat it as a call for your installer.
GoodWe warns that surroundings above 60°C can cause a fire, so keep heat sources away from the battery. For a burning smell, swelling or hissing, follow the emergency steps above. Our warning signs guide explains what each sign can mean.
Error codes and alerts
This selection of alarm names comes from the EHB and ET G2 inverter manuals and the Lynx Home F G2 battery manual.
| Alarm | What it means | Owner action |
|---|---|---|
| Utility Loss | Grid power not detected | Check for a blackout. It should clear when power returns |
| VAC Failure, FAC Failure, Grid Overvoltage | Grid voltage or frequency outside allowed limits | Often temporary. Report it if it keeps happening |
| Back-Up Over Load | Too much load on backed-up circuits | Switch off large appliances on backup |
| Over Temperature | Inverter running too hot | Check ventilation and shade. Call if it persists |
| Isolation Failure, Low Insulation Res | Low insulation resistance in the solar wiring | Don't touch anything. Call your installer |
| CT Connection Error | Current clamp wrongly placed or connected | Installer fix |
| Battery Overvoltage | Battery voltage too high | Call your installer |
| Battery Undervoltage | Battery voltage too low | Call your installer promptly |
| High Cell Temperature | Battery cells too hot | Check nothing hot is near the battery |
| Low Charging Temperature, Low Discharging Temperature | Battery too cold to work | Note the conditions. GoodWe's fix is a power-off until it warms, so call your installer |
| Insulation Fault (Lynx Home F) | Battery insulation problem | Do not touch the battery. Call your installer |
| Inconsistent Cell | Modules of different models fitted | Installer or dealer fix |
| BMU Communication Fault | Internal battery communication failed | Call your installer if it persists |
The Lynx Home F G2 manual maps each fault to its light pattern. Our guide to battery error codes explains what to tell your installer.
Restarting or shutting down
GoodWe's manuals set out a power-off order for technicians, and several alarm fixes say "power off and wait two hours". Those steps sit in manuals written for trained professionals, so ask your installer before attempting any of them.
In an emergency, use the shutdown sign if it is safe to do so. GoodWe also warns that a battery that won't start should be reported to after-sales straight away, or it may be permanently damaged.
When to call your installer or GoodWe
GoodWe's Lynx Home F G2 warranty asks owners to claim through the distributor or installer first. If that fails, you can raise a ticket on GoodWe's online support site. The warranty also says faults must be reported within one month of appearing.
Have this information ready:
- model, serial number and installation date
- the date the fault started and how often it happens
- the alarm text from SEMS Portal or SolarGo
- photos of the battery lights and the inverter lights
- what happened just before the fault, such as a storm, blackout or settings change
GoodWe Australia lists tech support on 03 9918 3905, Wi-Fi and communications support on 02 5104 0612, and [email protected] on its contact page. The warranty notes that Australian Consumer Law guarantees also apply. The ACCC explains these rights, and our warranty claims guide covers the process.
FAQ
Why did my battery level jump to 95 per cent in SEMS Portal?
GoodWe's EHB manual says this usually happens when communication with the battery management system fails. If the battery then goes into float charge, its displayed level is reset to 95 per cent. Check the COM light and tell your installer.
Can I change the battery settings myself?
Most battery settings sit behind a login in the SolarGo app, which installers use for setup. Ask your installer to make changes. GoodWe warns that choosing the wrong battery model can cause a system failure.
Sources
- Lynx Home F Series G2 User Manual, Australian edition (GoodWe manufacturer manual, accessed November 2026)
- ET G2 6-15kW with Lynx Home F and Lynx Home D User Manual, Australian edition (GoodWe system manual, accessed November 2026)
- EHB Series Hybrid Inverter User Manual (GoodWe inverter manual, accessed November 2026)
- EH Series Hybrid Inverter User Manual (GoodWe inverter manual, accessed November 2026)
- Lynx F G2 Series Datasheet, Australia (GoodWe datasheet, accessed November 2026)
- GoodWe Limited Warranty for Lynx Series LX F G2 Battery System, Australia and New Zealand (GoodWe warranty, accessed November 2026)
- Inverter offline on the SEMS Portal while the inverter's Wi-Fi has connected with the router (GoodWe online support article, accessed November 2026)
- Back-up function of the inverter (GoodWe online support article, accessed November 2026)
- GoodWe EHB series and GEH series Solar Inverters recall (Product Safety Australia, PRA 2025/20623, accessed November 2026)
- Contact GoodWe (GoodWe Australia contact page, accessed November 2026)
- Photovoltaic (PV) Array and Battery Energy Storage Systems fact sheet (South Australian Metropolitan Fire Service, accessed November 2026)
- Consumer rights and guarantees (ACCC, accessed November 2026)