When a SigenStor seems to misbehave, the cause is often one of three things: the system has lost its link to the Sigen cloud, a mySigen setting such as the operating mode or a cut-off SOC (state of charge) is doing what it was told, or the home has no Sigen Gateway for backup. Check the signal light on the energy controller, confirm the operating mode and cut-off values in mySigen, then look for an active alarm code. If you own a single-phase 8, 10 or 12 kW SigenStor, read the recall section below first.
Safety first
Sigenergy's user manual says there is high voltage inside the equipment, the casing must not be opened while it runs, and servicing is for trained electrical workers. The heat sink gets hot, so don't touch it. Keep the decorative cover uncovered and leave the 300 to 600 mm of clear space around it that the manual asks for. Never wash the unit with water, alcohol or oil.
Treat any of these as an emergency and keep people well back:
- smoke, fire, hissing or popping sounds
- a strange smell, leaking fluid or a battery pack that feels hot
- bulging or distorted packs, impact damage, or water reaching the unit
Sigenergy's emergency steps: if a battery pack smells abnormal, leaks or heats up, don't touch it and call a professional, and if a knocked or dropped unit gives off odour, smoke or fire, move away.
In a fire, leave the building and call the fire brigade; in Australia that is 000, the emergency number on Sigenergy's Australian safety data sheet. Tell the operator a home battery is involved, as South Australia's Metropolitan Fire Service advises, and wait out of any smoke. After a flood, don't touch a submerged battery and don't use the system again until your installer has checked it.
Your installation should have a shutdown procedure sign near the inverter and switchboard. Solar Victoria's guidance says it must be specific to your site, so read it now. For a wider list of warning signs, see battery noise, heat and smells.
Recall: single-phase 8, 10 and 12 kW energy controllers
Sigenergy Australia is recalling SigenStor EC 8.0/10.0/12.0kW SP AU energy controllers (PRA 2025/20703, published 19 November 2025). These are the single-phase 8, 10 and 12 kW energy controllers with quick connect AC plugs, sold nationally between 4 March 2025 and 18 November 2025. The notice says the AC plugs may overheat and become damaged, which is a fire risk, and that incidents have occurred.
How to check your unit. The notice says affected owners receive a notification in the mySigen app. Check that your system is a single-phase 8, 10 or 12 kW SigenStor, and look in the app for that message. If you're unsure, ask your installer or contact Sigenergy with your serial number.
What to do.
- Keep the system connected to the internet. A firmware update lets Sigenergy monitor each unit and temporarily reduce its AC output under sustained full load, which stops the plug overheating. The notice says all affected units that are online already have it.
- Wait to be contacted. Your retailer or a Sigenergy Australia service partner will arrange a free replacement with an updated AC plug, and Sigenergy adds an extra 2-year warranty.
Contact. The notice lists Sigenergy Australia Pty Ltd by email at [email protected], or the web page sigenergy.com/au/ac-replacement/end-user. Sigenergy's customer statement there adds that the temporary output limit is removed once your unit is replaced. Read the full recall notice on Product Safety Australia, and quote the PRA number if you contact a regulator.
Before you start: quick checks
- Signal light. If it's off, there's no cloud link. If it's green or blue but mySigen shows the system offline, Sigenergy's FAQ says to contact Sigen Service.
- Internet path. SigenStor connects by Ethernet, Wi-Fi or 4G through the Sigen CommMod. The 4G data supplied with the CommMod is free for 2 years, after which you top it up yourself.
- Operating mode. In mySigen, tap Mode on the Home screen, or Operational Mode under Setting.
- Cut-off and reserve values. Homeowners can view and set the charging and discharging cut-off SOC in system settings. With a Gateway installed, Backup Reserve sits on the Setting screen too.
- Weather. Below 0°C the battery heats itself before it can charge, which uses power. Above 40°C the system may reduce its output.
Reading the SigenStor lights
The energy controller has four indicators: solar (DC) side, AC side, batteries and network. Colour changes the meaning, so check what you see against the colour table in your user manual.
| Indicator | What it's telling you, according to Sigenergy |
|---|---|
| Solar (DC) side | Steady means connected, running or an inverter failure, depending on colour; flashing means a DC side fault; off means not connected |
| AC side | Steady shows on-grid running, off-grid running or a failure, depending on colour; flashing means off-grid overload or an AC fault |
| Batteries | Flashing means charging, discharging or some packs faulty, depending on colour; steady means idle or all packs faulty; off means the batteries are dormant |
| Network | Off means no link to the management system; flashing means connected to the local app or the CommMod is short of data; steady means online through Ethernet, Wi-Fi or 4G |
On the CommMod's network light, a short flash with a long gap means connecting, a long flash with a short gap means standby, and rapid flashing means data is moving.
Common problems and what to do
| Symptom | Likely cause | What you can check | When to call the installer |
|---|---|---|---|
| Battery won't charge | Charging cut-off reached, cold battery heating, mode settings | Cut-off SOC, operating mode, temperature, alarms | No charging for days with spare solar |
| Grid import at night | Discharging cut-off or Backup Reserve reached, Time-based Control periods | SOC versus your settings, current mode | Battery above its limits but idle |
| Offline in mySigen | Network down, 4G data used up | Signal light, router, data plan | Signal light green or blue but still offline |
| No power in a blackout | No Gateway, circuit not on backup, overload | Whether a Gateway is fitted, alarm 1021 | Backup fails with charge in the battery |
| Battery left low for a while | No solar plus a long outage, a fault or wrong settings | SOC in the app | Straight away if it can't recharge |
Battery won't charge
Start with your charging cut-off SOC, because the battery stops once it gets there, then check the operating mode. In Time-based Control, only the periods you set act as charging or discharging windows. Sigenergy's app note says any other time becomes a charging period when solar is available and a non-discharging period when it isn't.
If you've joined a virtual power plant, VPP mode can be managing the battery. Sigenergy says you can only leave VPP mode through the third-party VPP platform. Remote EMS mode similarly hands control to an outside energy management system.
Sigenergy's FAQ on solar not generating lists a related settings case: with export limited to zero, the battery at its charging cut-off and no household load, the panels stop producing. If the battery truly can't charge, the manual asks you to contact your installer promptly. Our battery not charging guide covers causes that apply to every brand.
Grid import at night
Discharging stops at the discharging cut-off SOC. If a Gateway is installed and Backup Reserve is set, the battery also stops at that reserve while the grid is on, keeping the rest for an outage. Check both values against the SOC in the app. Sigen AI Mode also works from your electricity prices, and Sigenergy's FAQ notes that with a negative tariff it may draw grid power instead of solar. See our guide to a battery not powering the home at night for general checks.
Offline in mySigen
Sigenergy's FAQ lists the causes: no working Ethernet, Wi-Fi or 4G link, the CommMod's monthly 4G data running out, or a network fault. Check your router, then any 4G plan. The FAQ's restart involves the AC and DC switches and a button under the decorative cover, so ask your installer to do that part.
Staying offline matters. Sigenergy's technical note says that after 90 consecutive days without a cloud connection, SigenStor switches to Safe Operation Mode. The user manual also warns that a system left inactive or offline for days may be switched off for safety if you don't respond to its reminder. More steps are in our battery offline in the app guide.
No power in a blackout
Sigenergy's backup layouts are built around a Sigen Gateway, while its non-backup layout has none. With a Gateway, the manual shows whole-home backup, or partial backup where only circuits on a backup board stay on. If you have no Gateway, ask your installer whether your system was designed for backup at all.
Backup time depends on the solar and battery available, and backed-up circuits can still go off if either falls short. Alarm 1021 means the off-grid output was overloaded or shorted, so switch off heavy appliances. Sigenergy's manual also says not to use the system with emergency medical equipment connected. Our backup not working in a blackout guide explains more.
Battery left low
The manual says a battery left low can be damaged by over-discharge. If the SOC is 10% or more, it should be charged within 30 days; below 10%, within 7 days. If yours can't recharge, call your installer quickly.
Alarm codes owners see most
These come from Sigenergy's alarm list in its Australian documentation packs. If an alarm persists, most entries point you to a Support troubleshooting page or your local service.
| Code | Name | What it means for you | What to do |
|---|---|---|---|
| 1003 | Over-temperature (inverter) | Too hot, poor airflow or direct sun | Check for blocked airflow; installer if it stays |
| 1004 | Equipment fault | An internal circuit fault | Installer; a power cycle is part of the fix |
| 1010 | Grid power outage | Grid down or AC switch off | Wait for the grid to return |
| 1018 | Communication fault | 4G data, internal, meter or Gateway link lost | Top up 4G data; installer for the rest |
| 1021 | Off-grid protection | Too much load, or a short, during backup | Switch off big loads |
| 1022 | Manual operation protection | The emergency rapid shutdown button was pressed | Release it only once the site is safe; ask your installer if unsure |
| 1023 | Abnormal wiring | AC wiring problem or Gateway breaker off | Installer |
| 2003 | Over-temperature (storage) | Battery or power module too hot | Check airflow; installer if it stays |
| 2004 | Equipment fault (storage) | Internal storage circuit fault | Installer |
| 2005 | Under-temperature | Battery too cold | Usually clears as it warms |
| 2007 | Battery module undervoltage | Battery voltage low, sometimes after long storage | Installer |
| 4001 | Communication fault | Gateway or meter link lost | Installer |
The full list is in the documentation packs linked under Sources.
Turning SigenStor off and on
The user manual's owner method is to tap Setting in mySigen and switch the device off or on. Its other method means removing the decorative covers to reach the switches, which is installer work. In an emergency, follow the shutdown sign at your switchboard if it is safe. If an alarm keeps returning after one power cycle, stop and call for help.
Model notes
- Manuals: single-phase systems have separate packs for 3 to 6 kW and 8 to 12 kW, and three-phase systems have their own. Each pack includes the alarm list.
- Battery packs are SigenStor BAT 5.0, 6.0, 8.0 and 10.0. Sigenergy won't accept liability for damage from mixing them with other batteries or another brand's inverter.
- The CommMod is the 4G module. Sigenergy recommends Ethernet or Wi-Fi where possible and notes the bundled data suits one device only.
When to call your installer or Sigenergy
Contact your installer if an alarm won't clear, the battery can't charge, backup failed despite charge in the battery, or after any impact, storm or flood. Have ready:
- the model and serial number, the alarm code and when it started
- screenshots of the mySigen alarm and your mode and SOC settings
Sigenergy's Australian warranty says claims start with a service ticket from the Support menu in mySigen, which gathers system details. It also asks for claims within 30 days of the failure and names installers and distributors as the default service channel. You can also email [email protected] or call Sigenergy Australia's service line on 0489 080 832. The consumer guarantees under the Australian Consumer Law apply as well; the ACCC says the business that sold you the product is the place to start. Our warranty claims guide has the detail.
FAQ
Can I run SigenStor without the internet?
Yes, Sigenergy says it works offline. After 90 days offline it enters Safe Operation Mode: the SOC range narrows to 10 to 90%, power is limited when cells are cold or hot, and updates stop. Full function returns once it reconnects.
Who can turn off Sigen AI Mode?
Only the owner's account. Sigenergy's FAQ says to open Sigen AI Mode under Operational Mode, tap the settings icon and choose disable.
Does the warranty depend on staying online?
Partly. The warranty says remote updates support the 10-year cover, and long periods offline may stop Sigenergy honouring it in full, although a 5-year warranty for the inverter and battery still applies.
Sources
- SigenStor documents, Sigenergy Australia Download Center (manufacturer download page, accessed November 2026)
- 8-12S Single Phase Sigen Energy Storage System Documentation (ZIP: SigenStor Home User Manual single-phase 8.0-12.0, Alarm list version 03, SigenStor Warranty AU and NZ) (manufacturer manual pack, accessed November 2026)
- 3-6S Single Phase Sigen Energy Storage System Documentation (ZIP: User Manual AU and Alarm list AU) (manufacturer manual pack, accessed November 2026)
- Technical Note: Safe Operation Mode after 90 days Cloud disconnection (Sigenergy technical note, accessed November 2026)
- Application note: How to set charging and discharging cut-off SOC and backup reserve on mySigen App (Sigenergy app note, accessed November 2026)
- Application note: How to set operation mode on mySigen App (Sigenergy app note, accessed November 2026)
- Sigenergy Australia FAQs (manufacturer support page, accessed November 2026)
- Sigenergy Safety Datasheet AU (manufacturer safety data sheet, accessed November 2026)
- Contact Sigenergy Australia (manufacturer contact page, accessed November 2026)
- SigenStor EC 8.0/10.0/12.0kW SP AU Energy Controllers recall (ACCC Product Safety Australia, accessed November 2026)
- Customer statement on single phase 8/10/12kW Energy Controllers (Sigenergy Australia, accessed November 2026)
- Photovoltaic (PV) Array and Battery Energy Storage Systems fact sheet (SA Metropolitan Fire Service, accessed November 2026)
- Technical guidance sheet 2.4: Labelling requirements for battery installations (Solar Victoria, accessed November 2026)
- Consumer rights and guarantees (ACCC, accessed November 2026)